| | Products | | |  Manufacturer: Contact:Mr. Fabricio Granados Category:Modules Analog Modules | AS-i Analog Module: 4 Thermocouple Type J InputsOrder No.:BW1933Description:The analog module has 4 thermocouple type J inputs.
The connection of the sensors is made by Combicon clamps. The temperature is measured using cold junction temperature compensation. The analog sensors are galvanical separated to AS-i.
The resolution of the analog data is 16 bit. The analog modules contain 50 Hz and 60 Hz filters. These filters can be optionally activated with the help of the AS-i parameters.
The conversion of the measured value and the data transmission via AS-i occur asynchronically according to the AS-i Profile 7.3.
For internal compensation the peripheral fault can be caused by a broken wire of the thermocouple. For the external compensation (PT-100 in connectors 2 and 3) the peripheral fault can also be caused by a broken wire or a short circuit of the PT-100 element. A short circuit of the TC cannot be recognised as an error.
Specification:V2.1Special Features:4 thermocouple type J inputs
Galvanical separation to AS-i
Profile 7.3 "Plug and Play"
as simple as digital AS-i I/O
Protection category IP20Product Link:www.bihl-wiedemann.de/deutsch/catalog/1933/1933.ht… |
Last updated: 07/03/2008 |
| |